Current Carrying Capacity of Cables with Improved Characteristics in Case of Fire
Bayka products
The values given below are applicable to these products:
Column N2XH [copper, without concentric conductor and braid] (with CPR or nonfire):
Power Soil | Telekom-Power |
Column N2XCH/N2XCWH [copper, with concentric conductor or braid] (with CPR or nonfire):
soilblack EMC | soilblack VFD EMC |
General
This section applies to the capacity under both agreed but also deviating conditions, provided that three cores are loaded in three-phase operation or only one single-core cable is loaded in DC operation.
The rated currents listed in the tables are recommended values under normal operating conditions.
General Conditions
Temperatures °C (conductor) | |
---|---|
maximum admissible operating temperature | +90 |
maximum admissible temperature in case of short circuit | +250 |
Concentric conductors are grounded on both ends.
Operating frequency 50 Hz.
The tabulated loading capacities are based on various conditions such as
– operating mode,
– laying conditions,
– environmental conditions.
In the event of deviating operating conditions, the loading capacities are to be multiplied by suitable conversion factors, which are based on the same calculation principles and operating conditions as the given values.
Current-Carrying Capacities of Cables with Improved Characteristics in Case of Fire
Laying in air(30°C)
recommended values acc. to HD 604 S1, table B.1
N2XH [copper, without concentric conductor and braid] |
N2XCH / N2XCWH [copper, with concentric conductor or braid] |
||||
---|---|---|---|---|---|
number of loaded cores |
3 | 3 | 1 | 3 | 3 |
cross-section mm² |
copper conductor rated current in A |
||||
1,5 | 26 | 24 | 33 | 27 | 25 |
2,5 | 34 | 32 | 43 | 36 | 33 |
4 | 44 | 42 | 57 | 47 | 43 |
6 | 56 | 53 | 72 | 59 | 54 |
10 | 77 | 74 | 99 | 81 | 75 |
16 | 102 | 98 | 131 | 109 | 100 |
25 | 138 | 133 | 177 | 146 | 136 |
35 | 170 | 162 | 217 | 179 | 165 |
50 | 207 | 197 | 265 | 218 | 201 |
70 | 263 | 250 | 336 | 275 | 255 |
95 | 325 | 308 | 415 | 336 | 314 |
120 | 380 | 359 | 485 | 388 | 364 |
150 | 437 | 412 | 557 | 438 | 416 |
185 | 507 | 475 | 646 | 501 | 480 |
240 | 604 | 564 | 774 | 580 | 565 |
300 | 697 | 649 | 901 | 654 | 643 |
400 | 811 | 761 | 1060 | 733 | 737 |
500 | 940 | 866 | 1252 | 825 | 807 |
*) rated current in DC plants with far off return conductor
Current Carrying Capacity of Cables with Improved Characteristics in Case of Fire
Admissible short-circuit temperatures and rated short-circuit current densities
cables with | admissible short-circuit temperature °C |
rated short-circuit current densities in A/mm² for a rated short-circuit duration of 1s |
|||||||
conductor temperature at the beginning of short-circuit in °C | |||||||||
90 | 80 | 70 | 60 | 50 | 40 | 30 | 20 | ||
copper conductor | 250 | 143 | 149 | 154 | 159 | 165 | 170 | 176 | 181 |
Conversion factors for different numbers of loaded cores of multi-core cables in air
acc. to HD 627 S1, part 7H, table A.1
number of loaded cores |
Laying in air |
---|---|
5 | 0,75 |
7 | 0,65 |
10 | 0,55 |
14 | 0,50 |
19 | 0,45 |
24 | 0,40 |
40 | 0,35 |
61 | 0,30 |