Current carrying capacity

flexible copper cables and wires

acc. to  DIN VDE 0298-4 (VDE 0298-4):2023-06

Bayka products
The values given below are applicable to these products:

Product area BayMotion® (with and without CPR or nonfire):

EMC PUR EMC-UV-Flex Control Flex Power + Flex Power + EMC
Metro Power + Power PUR Power Soil
PTTA soilblack EMC soilblack VFD EMC Telekom-Power
Tram VFD EMC PUR VFD EMC Soil

General
When selecting the conductor cross-section, other criteria may have to be taken into account, such as requirements for protection against electric shock (see DIN VDE 0100-410), for protection against thermal influences (see DIN VDE 0100-420), for protection against overcurrent (see DIN VDE 0100-430), the voltage drop (see DIN VDE 0100-520) and for the limit temperatures of terminals to which the conductors are connected.
The rated currents listed in the tables are recommended values for uninterrupted operation.
They apply to operation with alternating or three-phase current with a frequency of 50 Hz to 60 Hz and with direct current.

Recommended values

Excerpt from DIN VDE 0298-4 (VDE 0298-4):2023-06 table 11

1 2 5
Laying type a free in air
on or at areas

single core

  • rubber insulated
  • PVC-insulated
  • heat resistant

multi-core cables (not for household or handheld devices)

  • rubber insulated
  • PVC-insulated
Number of loaded cores 1 2 or 3
cross section

copper conductor

mm²

current carrying capacity

A

current carrying capacity

A

0,5
0,75 15 12
1 19 15
1,5 24 18
2,5 32 26
4 42 34
6 54 44
10 73 61
16 98 82
25 129 108
35 158 135
50 198 168
70 245 207
95 292 250
120 344 292
150 391 335
185 448 382
240 528 453
300 608 523
400 726
500 830
conversion factors for

different ambient temperature

table 10 table 10

accumulation

table 10 table 22

laying under the ceiling

table 22

multi-core cables

table 27
A For a list of the types and the permissible operating temperature on the conductor, see Table 1.

Further conditions, assumptions, installation methods, calculation formulas, etc. see standard.


Current-carrying capacity multicore cables

Excerpt from DIN VDE 0298-4 (VDE 0298-4):2023-06 table 27

Conversion factors for multicore cables and wires with nominal conductor cross-sections up to 10 mm²

number of
loaded cores
laying in air
5 0,75
7 0,65
10 0,55
14 0,50
19 0,45
24 0,40
40 0,35
61 0,30

Further conditions, assumptions, installation methods, calculation formulas, etc. see standard.

Excerpts from DIN VDE 0298-4 (VDE 0298-4):2023-06 are reproduced for the registered limited edition with permission 32.024 from the DIN German Institute for Standardization e.V. and the VDE Association of Electrical Engineering Electronics Information Technology e.V.. For further reproductions or editions is a separate permit is required. The versions with the latest issue date, which are available from VDE VERLAG GMBH, Bismarckstr., are decisive for the application of the standards. 33, 10625 Berlin, www.vde-verlag.de, and Beuth Verlag GmbH, 10772 Berlin, www.beuth.de.